ITEM DESCRIPTION
The Address item sets the main network address of the
room pressure monitor. Each unit on the network must
have its own unique address.
NOTE: The Address item is only functional when
Comm Type is set to MODBUS or BACNET.
NOTE: Changes to the Address may take up to 1 minute
to take effect when using BACnet
communications.
The MAC ID item combines with the MAC ADDRESS to
form the Device ID. The Device ID is the 3 digits of the
MAC ID*1000 plus the 3 digits of the MAC ADDRESS. For
example, if the MAC ID is 865 and the MAC ADDRESS is
1, then the Device ID is 865001.
NOTE: The MAC ID item is only functional when
Comm Type is set to BACNET.
NOTE: Changes to the MAC ID may take up to 1 minute
to take effect when using BACnet
communications.
The Baud Rate item sets the communication speed of the
PresSura monitor when using Modbus or BACnet
communications.
NOTE: Changes to the Baud Rate may take up to
1 minute to take effect when using BACnet
communications.
Baud Rate is not configurable when Comm Type
is set to Modbus.
DEFAULT
ITEM RANGE
VALUE
1
Modbus: 1 to 247
BACnet: 1 to 127
1 to 999
606
Modbus: 9600
Modbus: 9600
BACnet: 9600,
BACnet:
19200, 38400,
AutoBaud
76800, AutoBaud