Pressura RPM10 Operation And Service Manual page 84

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

RPM10 Variable List
Variable Name
13
Input 7
Configuration
14
Room 1 Mode
15
Room 1 Low Alarm
Enable
16
Room 1 High Alarm
Enable
17
Room 1 Negative
Low Alarm Setpoint
18
Room 1 Negative
High Alarm Setpoint
19
Room 1 Positive
Low Alarm Setpoint
20
Room 1 Positive
High Alarm Setpoint
21
Low Exhaust Alarm
22
Low Supply Alarm
61
Alarm Reset
62
Audible Alarm
Enable
63
Alarm Delay
64
Mute Timeout
65
Door Delay
66
Modbus Address
67
Output 1 Signal
Type
71
Output 2 Signal
Type
72
Output 2 Range
73
Output 2 Signal
74
Output 2 Value
76
Variable
Address
Read/Write
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read
Read
Read
Read
Read
Read
Integer DDC system receives
2
Exhaust Pressure Flow
3
Exhaust Linear Flow
4
Exhaust Venturi
5
Exhaust Switch
8
None
1
Positive
2
Negative
3
No Isolation
1
Disabled
2
Enabled
1
Disabled
2
Enabled
Displayed in inches H
O.
2
Host DDC system must divide value by
100,000 to report pressure correctly
Displayed in inches H
O.
2
Host DDC system must divide value by
100,000 to report pressure correctly
Displayed in inches H
O.
2
Host DDC system must divide value by
100,000 to report pressure correctly
Displayed in inches H
O.
2
Host DDC system must divide value by
100,000 to report pressure correctly
Displayed in cfm
Displayed in cfm
1
Latched
2
Unlatched
1
On
2
Off
Displayed in seconds
Displayed in minutes
Displayed in seconds
1
None
1
None
2
Room 1 Pressure Output
3
Room 1 Exhaust Flow Output
If Pressure: Displayed in inches H
Host DDC system must divide value by
100,000 to report pressure correctly
If Flow: Displayed in cfm
1
4-20 mA
2
0 to10 VDC
0 to 100%
O.
2
Appendix B