Pressura RPM10 Operation And Service Manual page 55

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input3 Config Menu
TSI Sensor
SOFTWARE
MENU ITEM
NAME
Set Sensor
Elevation
Elevation
RPM20
Reset Calibration
Reset Cal
RPM20
Check Sensor
Check Status
Status
RPM20
ITEM DESCRIPTION
The Elevation item is used to enter the elevation of the
sensor above sea level. The pressure value needs to be
corrected due to changes in air density at different
elevations.
While this number can be entered in increments of 1 foot,
the density adjustments are in 1,000 foot increments. For
example, if the PresSura will interpret Elevation settings
between 0 and 999 feet as 0 feet, settings between 1000
and 1999 feet as 1000 feet, etc.
The Reset Cal item is used to return to the factory default
calibration, undoing field calibration adjustments. When
this menu item is entered, the controller will prompt the
user to verify that they want to do this by displaying the
message "Reset Settings to Factory Default?" Entering
YES resets the Sensor Zero, Sensor Span and Elevation
items to defaults. Entering NO will cancel the reset.
The Check Status item is used to check the communication
status of the sensor. After pressing the button, the
PresSura unit will respond with:
COMM ERROR - DIM cannot communicate with sensor.
Check all wiring and the pressure
sensor address.
SENS ERROR
- Physical damage to pressure sensor
circuitry. Unit is not field-repairable.
Send to TSI for repair.
CAL ERROR
- Calibration data lost. Send to TSI for
calibration.
DATA ERROR
- Problem with sensor EEPROM, field
calibration or analog output. Check all
data configured and confirm unit is
functioning correctly.
DEFAULT
ITEM RANGE
VALUE
0 to 10,000 feet
0
above sea level
None
N/A
None
N/A