Rm2 Alarm Menu

SOFTWARE
MENU ITEM
NAME
Mode of Room 2
Room Mode
RPM20
Room 2 Alarm
Alarm Enable
Enable
RPM20
Room 2 Negative
Neg Low Alm
Low Alarm
RPM20
Room 2 Negative
Neg Hi Alm
High Alarm
RPM20
Room 2 Positive
Pos Low Alm
Low Alarm
RPM20
ITEM DESCRIPTION
The Room Mode item selects the room pressure
direction. This item enables all related alarms, for
pressure direction selected. Selecting ROOM1 means that
the Room Mode will follow the Room Mode of Room 1.
NOTE: No Isolation Room Mode can be selected from the
main running screen.
The Alarm Enable item enables the low and high alarm
functions. When this item is entered, the monitor will show
buttons for Low Alarms and High Alarms. Press the button
to toggle between enabling and disabling the alarms.
The Neg Low Alm item sets the negative low pressure
alarm setpoint. A low alarm condition is defined as when
the magnitude of the room pressure falls below the Neg
Low Alm setpoint.
This item is enabled when the TSI key switch is in
negative room pressure position or when NEGATIVE is
selected in Room Mode item.
The Neg Hi Alm item sets the negative high pressure
alarm setpoint. A high alarm condition is defined as when
the room is more negative than the Neg Hi Alm setpoint.
This item is enabled when the TSI key switch is in
negative room pressure position or when NEGATIVE is
selected in Room Mode item.
The Pos Low Alm item sets the positive low pressure
alarm setpoint. A low alarm condition is defined as when
the room is less positive than the Pos Low Alm setpoint.
This item is enabled when the TSI key switch is in positive
room pressure position or when POSITIVE is selected in
Room Mode item.
ITEM RANGE
DEFAULT VALUE
Positive
Negative
Negative
Room1
Enabled
Low Alarms
Disabled
Enabled
High Alarms
Disabled
-0.19500 in H
O to
-0.01000 in H
2
+0.19500 in H
O
2
Note: Neg Low Alm
cannot be set
more negative
than the Neg Hi
Alm
-0.19500 in H
O to
-0.10000 in H
2
+0.19500 in H
O
2
Note: Neg Hi Alm
cannot be set
less negative
than the Neg
Lo Alm
-0.19500 in H
O to
0.01000 in H
2
+0.19500 in H
O
2
Note: Pos Low Alm
cannot be set
more positive
than the Pos Hi
Alm
O
2
O
2
O
2