Input3 Config Menu
Sup Venturi
SOFTWARE
MENU ITEM
NAME
Reset Calibration
Reset Cal
RPM10 and
RPM20
Input3 Config Menu

Supply Switch

SOFTWARE
MENU ITEM
NAME
Low Flow Alarm
Low Flow Sig
Signal
RPM10 and
RPM20
Input3 Config Menu
TSI Sensor
SOFTWARE
MENU ITEM
NAME
Set Sensor Zero
Sensor Zero
Calibration
RPM20
Set Sensor Span
Sensor Span
Calibration
RPM20
ITEM DESCRIPTION
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments.
When this menu item is entered, the controller will prompt
the user to verify that they want to do this by displaying the
message "Reset Settings to Factory Default?" Entering
YES resets the K-Factor factor for this sensor to defaults.
Entering NO will cancel the reset.
ITEM DESCRIPTION
The Low Flow Sig item sets the signal the Model RPM10
or RPM20 Room Pressure Monitor will receive to indicate a
low supply flow condition.
ITEM DESCRIPTION
The Sensor Span item is used to re-zero the TSI Sensor
zero calibration point.
The Sensor Span item is used to match or calibrate the
PresSura monitor TSI sensor to the average room
pressure velocity as measured by a portable air velocity
meter.
DEFAULT
ITEM RANGE
VALUE
None
N/A
DEFAULT
ITEM RANGE
VALUE
Open, Closed
Closed
DEFAULT
ITEM RANGE
VALUE
None
Unit is factory
calibrated and
should not
need
adjustment.
None
Unit is factory
calibrated and
should not
need
adjustment.