Input1 Config Menu; Tsi Sensor - Pressura RPM10 Operation And Service Manual

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input1 Config Menu

TSI Sensor

SOFTWARE
MENU ITEM
NAME
Set Sensor Zero
Sensor Zero
Calibration
RPM10 and
RPM20
Set Sensor Span
Sensor Span
Calibration
RPM10 and
RPM20
Set Sensor
Elevation
Elevation
RPM10 and
RPM20
Reset Calibration
Reset Cal
RPM10 and
RPM20
ITEM DESCRIPTION
The Sensor Zero item is used to re-zero the TSI Sensor
zero calibration point.
The Sensor Span item is used to match or calibrate the
PresSura TSI sensor to the average room pressure velocity
as measured by a portable air velocity meter.
The Elevation item is used to enter the elevation of the
sensor above sea level. The pressure value needs to be
corrected due to changes in air density at different
elevations.
While this number can be entered in increments of 1 foot,
the density adjustments are in 1,000 foot increments. For
example, if the PresSura will interpret Elevation settings
between 0 and 999 feet as 0 feet, settings between 1000
and 1999 feet as 1000 feet, etc.
The Reset Cal item is used to return to the factory default
calibration, undoing field calibration adjustments. When this
menu item is entered, the monitor will prompt the user to
verify that they want to do this by displaying the message
"Are You Sure." Entering YES resets the Sensor Zero,
Sensor Span and Elevation items to defaults. Entering NO
will cancel the reset.
DEFAULT
ITEM RANGE
VALUE
None
Unit is factory
calibrated and
should not need
adjustment.
None
Unit is factory
calibrated and
should not need
adjustment.
0 to 10,000 feet
0
above sea level
None
N/A