Configure Menu

MENU ITEM
SOFTWARE
Monitor/
NAME
Controller
Number of Rooms
# of Rooms
Monitored
RPM10 and
RPM20
Number of
Press Modes
Pressure Mode
Selections
RPM10 and
RPM20
Label for Room 1
Rm1 Label
RPM10 and
RPM20
Label for Room 2
Rm2 Label
RPM20
ITEM DESCRIPTION
The # of Rooms item selects the number of rooms the
Model RPM10 and RPM20 monitor will monitor and
control.
The Press Modes item determines the room modes
available for selection when the user presses the Room
Mode button on the main running screen.
Press Mode
Room Mode Selections on Screen
2 Buttons
Positive / No Isolation
Or
Negative / No Isolation
(based on Room Mode item in
respective Alarm menu)
3 Buttons
Negative / No Isolation / Positive
W A R N I N G
Codes and Standards in the US and many other areas of
the world do not allow a room to be switched from Positive
to Negative Isolation. Consult local authorities before
setting Press Modes to 3 Buttons.
The Rm1 Label item allows the user to set the room
number or other designator for room 1.
The Rm2 Label item allows the user to set the room
number or other designator for room 2.
NOTE: Rm2 Label is only active if the # of Rooms item
is set to 2 Rooms with Anteroom.
ITEM RANGE
DEFAULT VALUE
1 Room
RPM10: 1 Room
RPM20: 1 Room,
1 Room with
Anteroom, 2 Rooms
with Anteroom
2 Buttons, 3 Buttons
2 Buttons
13 characters of text
ROOM 1
13 characters of text
ROOM 2