Supply/Exhaust Switch Calibration
NOTE:
1. Set the LOW FLOW SIG to match the low flow indication from the switch. OPEN means the
switch will open to indicate low flow. CLOSED means the switch will close to indicate low
flow.
Door Switch Configuration
NOTE:
1. Set the DR OPEN SIGN to match the door open indication from the switch. OPEN means the
switch will open to indicate the door is open. CLOSED means the switch will close to indicate
the door is open.
Temperature Sensor Configuration
NOTE:
1. Adjust the SENSOR SPAN so the displayed temperature matches a reference measurement.
Use the RESET CAL item to reset the SENSOR SPAN back to the factory default.
Relative Humidity Sensor Configuration
NOTE:
1. Set the SENSOR MIN to the minimum reading of the relative humidity sensor. This is
usually 0%.
2. Set the SENSOR MAX to the maximum reading of the relative humidity sensor. This is
usually 100%.
3. Set the SIGNAL MAX to the minimum output voltage of the relative humidity sensor. This is
usually 0 V.
4. Set the SIGNAL MAX to the maximum output voltage of the relative humidity sensor. This is
usually 10 V.
5. Adjust the SENSOR SPAN so the displayed relative humidity matches a reference
measurement.
Use the RESET CAL item to reset the SENSOR SPAN back to the factory default.
62
Flow switches are optional and may not be installed in your system.
Flow switches do not actually measure the flow, but are designed to
provide an open or closed signal to indicate the presence or absence
of flow.
Door switches are optional and may not be installed in your system.
Temperature sensors are optional and may not be installed in your
system.
Relative Humidity sensors are optional and may not be installed in
your system.