Press Trans - Pressura RPM10 Operation And Service Manual

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input1 Config Menu
TSI Sensor
SOFTWARE
MENU ITEM
NAME
Check Sensor
Check Status
Status
Input1 Config Menu

Press Trans

SOFTWARE
MENU ITEM
NAME
Set Minimum
Sensor Min
Sensor Pressure
Output
RPM10 and
RPM20
Set Maximum
Sensor Max
Sensor Pressure
Output
RPM10 and
RPM20
ITEM DESCRIPTION
The Check Status item is used to check the communication
status of the sensor. After pressing the button, the PresSura
unit will respond with:
COMM ERROR - DIM cannot communicate with
sensor. Check all wiring and the
pressure sensor address.
SENS ERROR - Physical damage to pressure sensor
circuitry. Unit is not field-repairable.
Send to TSI for repair.
CAL ERROR
- Calibration data lost. Send to TSI for
calibration.
DATA ERROR - Problem with sensor EEPROM, field
calibration or analog output. Check all
data configured and confirm unit is
functioning correctly.
ITEM DESCRIPTION
The Sensor Min item is used to set the minimum reading
of a pressure transducer used to measure room pressure
differential. For example, if the pressure transducer has a
range of -0.25 in H
O to +0.25 in H
2
the Sensor Min should be set to -0.25 in H
The Sensor Max item is used to set the maximum reading
of a pressure transducer used to measure room pressure
differential. For example, if the pressure transducer has a
range of -0.25 in H
O to +0.25 in H
2
the Sensor Max should be set to +0.25 in H
ITEM RANGE
ITEM RANGE
-1.00 to + 1.00 in H
O (-62.5 to +62.5 Pa),
2
O (-62.5 Pa).
2
-1.00 to + 1.00 in H
O (-62.5 to +62.5 Pa),
2
O (+62.5 Pa).
2
DEFAULT
VALUE
None
N/A
DEFAULT
VALUE
O
0
2
O
0
2