Pressura RPM10 Operation And Service Manual page 64

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input7 Config Menu
Exh Lin Flow
SOFTWARE
MENU ITEM
NAME
Set Maximum
Sensor Max
Sensor Output
RPM10 and
RPM20
Set Minimum
Signal Min
Sensor Voltage
Output
RPM10 and
RPM20
Set Maximum
Signal Max
Sensor Voltage
Output
RPM10 and
RPM20
Reset Calibration
Reset Cal
RPM10 and
RPM20
ITEM DESCRIPTION
The Sensor Max item is used to set the maximum reading
of a flow station used to measure exhaust air flow. The
Sensor Max item has increments of 1000 fpm.
The Signal Min item is used to set the minimum output
signal when a flow station and pressure transducer is used
to measure exhaust air flow
The Signal Max item is used to set the maximum output
signal when a flow station and pressure transducer is used
to measure exhaust air flow.
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments.
When this menu item is entered, the controller will prompt
the user to verify that they want to do this by displaying the
message "Reset Settings to Factory Default?" Entering
YES resets the K-Factor factor for this sensor to defaults.
Entering NO will cancel the reset.
DEFAULT
ITEM RANGE
VALUE
0 to 10,000 fpm
0
0 to 10 V
0 V
1 to 10 V
10 V
None
N/A