Q48: Download CSID (6 Digits)
DEFAULT: 000000
The system supports a six (6)‐digit CSID code that is used for
remote telephone programming of the Control Panel. This
code is verified when the Control Panel connects with the
downloading software. If the CSID code doesn't match the
downloading software, the Control Panel will deny the
connection.
•
The CSID code can be entered manually with this
programming question.
•
If this field is left with the default (000000), the first
time the downloading software connects with the
Control Panel, the field will be filled with the
software's CSID.
Q49: Programming Mode Entry Reports
to CS (0-1)
DEFAULT: (0) Disabled
A report can be sent to the Central Station any time installer
programming mode is entered and exited.
•
The default setting (0) Disabled prevents reporting
programming mode entry and exit.
•
To report programming mode entry and exit, select
(1) Enabled.
NOTE: This report can only be sent through the telephone
dialer. It is not supported through the GSM (Cellular)
Radio Module.
Q50: Trouble Reports to CS (0-1)
DEFAULT: (1) Enabled
Trouble reports can be sent to the Central Station when any
sensor trouble condition occurs.
•
The default setting (1) Enabled allows reporting
sensor trouble conditions.
•
To not report sensor trouble conditions, select (0)
Disabled.
NOTE: This setting does not affect trouble reports caused
by Control Panel conditions, only trouble reports caused
by sensors.
Q51: Manual Bypass Reports to CS (0-1)
DEFAULT: (0) Disabled
Manual bypass reports can be sent to the Central Station
when any sensor has been manually bypassed by the user.
•
The default setting (0) Disabled prevents sending
manual bypass reports.
•
To allow sending manual bypass reports, select (1)
Enabled.
Q52: AC Loss Reports to CS (0-1)
DEFAULT: (1) Enabled
AC power loss reports can be sent to the Central Station if
the Control Panel loses AC power.
•
The default setting (1) Enabled allows AC power loss
reports.
•
To turn off AC power loss reports, select (0)
Disabled.
NOTE: The AC power will have to be absent from the
Control Panel for the time set by programming question
Q38 before the AC power loss trouble alert
displayed (the default is 10 minutes). If programming
question Q39 is enabled, the actual AC power loss
report will occur at a random time of up to four hours
after the AC power loss trouble alert
NOTE: The Control Panel's AC power icon displays the
power status immediately. A red "X" over the icon
indicates no AC power.
Q53: System Low Battery Reports to CS
(0-1)
DEFAULT: (1) Enabled
Low battery reports can be sent to the Central Station if the
Control Panel's battery tests low.
•
The default (1) Enabled allows Control Panel low
battery reports.
•
To turn off Control Panel low battery reports, select
(0) Disabled.
Q54: RF Low Battery Reports to CS (0-1)
DEFAULT: (1) Enabled
Sensor low battery reports can be sent to the Central
Station if a sensor battery tests low and sends a low battery
transmission to the Control Panel.
•
The default setting is (1) Enabled and allows the
system to send low battery reports for sensors.
•
To turn this feature OFF, select (0) Disabled.
Q55: Opening Reports to CS (0-1)
DEFAULT: (0) Disabled
Opening reports can be sent to the Central Station each
time the system is disarmed. The user or key fob number is
indicated in the opening report.
•
The default setting (0) Disabled prevents opening
reports.
•
To allow opening reports, select (1) Enabled.
Q56: Closing Reports to CS (0-1)
DEFAULT: (0) Disabled
Closing reports can be sent to the Central Station each time
the system is armed. The user or key fob number is
indicated in the closing report. If Quick Arming is enabled,
User #0 is indicated for the closing report.
•
The default setting (0) Disabled prevents closing
reports.
•
To allow closing reports, select (1) Enabled.