Nfpa Standard 72 - 2gig Technologies Go!Control Panel Installation & Programming Manual

Wireless security system
Hide thumbs Also See for Go!Control Panel:
Table of Contents

Advertisement

NFPA STANDARD 72
Smoke detectors must be installed in accordance with National Fire Protection Association (NFPA) Standard 72: National 
Fire Alarm and Signaling Code, which reads as follows: 
"2‐1.1.1 Smoke alarms shall be installed outside of each separate sleeping area in the immediate vicinity of the 
bedrooms and on each additional story of the family living unit including basements and excluding crawl spaces and 
unfinished attics. In new construction, a smoke alarm shall be installed in each sleeping room.
2‐1.1.2 For family living units with one or more split levels (i.e., adjacent levels with less than one full story separation 
between levels), a smoke alarm shall suffice for an adjacent lower level, including basements. (Exception: Where there 
is an intervening door between one level and the adjacent lower level, a smoke alarm shall be installed on the lower 
level.)
Ceiling mounted smoke alarms should be located in the center of the room or hall, or not less than 4 inches from 
any wall. When the alarm is mounted on a wall, the top of the alarm should be 4 to 12 inches from the ceiling.
Do not install smoke alarms where normal ambient temperatures are above 100°F (37.8°C), or below 40°F (4°C). 
Also, do not locate alarm in front of air conditioners, heating registers, or other locations where normal air 
circulation will keep smoke from entering the detector.
A‐2.5.2.1 Smoke Detection ‐ Are More Smoke Alarms Desirable? The required number of smoke alarms might not 
provide reliable early warning protection for those areas separated by a door from the areas protected by the required 
smoke alarms. For this reason, it is recommended that the residential user consider the use of additional smoke alarms 
for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace 
room, utility room, and hallways not protected by the required smoke alarms. The installation of smoke alarms in 
kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally 
experience conditions that can result in improper operation or false alarms."
NOTE: Smoke alarms are not to be used with detector guards unless the combination has been evaluated and found 
suitable for the purpose.
Figure 21 Recommended Smoke Alarm Locations
24
    Copyright ©  2014 Linear LLC

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Go!Control Panel and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents

Save PDF