Q39: Random AC Loss Report Time (0-1)
DEFAULT: (1) Enabled
This feature allows the system to report AC power loss and 
AC power restore at a random time of up to 45 minutes 
after the event occurs. This helps to reduce Central Station 
congestion due to a wide‐spread power outage affecting 
many Control Panels at once. The random AC power status 
report timer is triggered based on the time set by Q38: 
Random AC Loss Report Time.
The default setting (1) Enabled turns this feature 
ON. 
To turn this feature OFF, select (0) Disabled.
Q40: CS #2 Phone Number (0-25 digits)
DEFAULT: No Default
The telephone number for Central Station #2 can be up to 
25 digits. Central Station telephone #2 is dialed as backup in 
case telephone #1 does not connect.
Enter the Central Station #2 telephone number.
The Shift button accesses the pound and star 
symbols. The P button adds a 3‐second pause to the 
dialing.
Q41: CS #2 Account Number (4 Digits)
DEFAULT: No Default
The account number for Central Station #2 is always four 
digits and can include some alpha characters.
Enter four (4) digits for the Central Station #2 
account number.
The Shift button accesses B, C, D, E, and F 
characters.
Q42: Remote Control Phone (0-3)
DEFAULT: (3) Data and Voice
This setting controls remote telephone access to the 
system. 
The data option is for the installer. It allows access 
for programming and operating the system with 
custom PC downloader software.
The voice option is for the subscriber. It allows the 
subscriber to call the system from an off‐site phone, 
to get the status of the system, and to perform 
remote commands. These commands are executed 
by entering touch tones. The status is reported back 
via voice prompts. A valid User Code is required for 
remote telephone access. The user can perform the 
following functions: arm in any mode, disarm, 
bypass, get system status, and turn on or turn off 
the open collector output.
If voice access is enabled, to connect to the panel, the 
subscriber will need to call the telephone number that the 
Control Panel is connected to, wait for one or two rings, 
then hang up. The subscriber needs to call again, within 10‐
45 seconds. The Control Panel answers the call.
When the panel answers the phone, the user will be 
prompted to enter their code. If a valid code is entered, the 
system will announce the current system status. If an invalid 
code is entered, the panel will ask for the code again. After 
two invalid attempts, the panel will disconnect. After two 
calls, with two invalid attempts each, the panel will lock out. 
The lock out will last for 30 minutes.
The default setting is (3) Data and Voice.
To use data access only, select (1) Data Only.
To use voice access only, select (2) Voice Only.
To turn the remote access feature OFF, select (0) 
Disabled.
Telephone 
Remote Control Phone 
Key
Mode
1
System status report
2
Arm the system in Away mode
3
Arm the system in Stay mode
4
Disarm the system
5
Turn on the auxiliary output
6
Turn off the auxiliary output
7
Stop the system status report
8
Disconnect (hang up)
9
Repeat command menu
#
Bypass all open sensors and arm 
system
NOTE: Remotely arming the system to Away mode will not 
start an Exit Delay or activate Auto Stay mode (if 
enabled).
Copyright © 2014 Linear LLC
Control Panel Programming
59