(16) 24-Hour Fire with Verification †
This sensor type is continuously armed 24‐hours a day. A
sensor programmed to this type can trigger the local alarm
fire sounder and the bell output regardless of the mode the
system is in. Typical use would be for wireless smoke
detectors. This sensor type is always active and cannot be
bypassed.
For verification, this sensor type must be violated twice in
two (2) minutes, or remain violated for 30 seconds. If any
other fire sensor (verified sensor type or not) violates
within two minutes, both sensors will cause a fire alarm.
(23) No Response Type
This sensor type is a special zone that can be monitored for
activity or inactivity by the Central Station. It does not affect
security system status.
(24) Silent Burglary
This sensor type is for silent triggering the burglary alarm
with perimeter doors and windows that will not be used to
enter or exit the protected premises while the system is
armed. The Control Panel's sounder and the bell output will
not activate.
An instant silent alarm will occur when this type of sensor is
triggered with the system armed in either the Stay or Away
mode.
† Indicates Sensor types that are not allowed for
hardwire loops.
Sensor Types (Zones)