Dx2010 Input Expander - Bosch ICP-EZM2 System Reference Manual

Easy series control panel
Hide thumbs Also See for ICP-EZM2:
Table of Contents

Advertisement

Easy Series Control Panel
Display
Color
Single red rotating segment
Broken red circle
Table 8.3: System On (Unoccupied) Display States
8.3

DX2010 Input Expander

Notice!
If Points 9 to 32 contain wired and wireless points, install all required DX2010 Input
Expanders before adding any wireless points to the system.
The DX2010 Input Expander connects directly to the data bus of a compatible control panel.
Each expander adds eight input loops.
DX2010 Input Expander
Operating Voltage:
Current Draw:
Outputs:
Sensor Loop Terminal Wire Size: 0.8 mm (22 AWG) to 1.8 mm (14 AWG)
Wire Length:
Operating Temperature:
Relative Humidity:
Sensor Loop Resistance:
Sensor Loop:
Add a DX2010 Before Adding Wireless Points
The control panel supports up to three DX2010 modules. Each module occupies a group of
eight points.
The DX2010's DIP switch address determines which group of points the DX2010 occupies:
As each DX2010 module is added to the system, it occupies the next available group of points.
For Points 9 to 32, wireless points also occupy points in the same groups of eight as the
DX2010 modules:
Bosch Security Systems, Inc.
8 VDC to 14 VDC
35 mA standby; 135 mA maximum with connected accessories
100 mA, 12 VDC supervised output for accessories
Control panel to DX2010 (DX2010 auxiliary output not used):
0.8 mm (22 AWG) = 305 m (1000 ft)
1.2 mm (1.2 mm) = 610 m (2000 ft)
Control panel to DX2010 (DX2010 auxiliary output supplying 100 mA):
0.8 mm (22 AWG) = 30 m (100 ft)
1.2 mm (1.2 mm) = 76 m (250 ft)
0°C to +50°C (+32°F to +122°F)
5% to 85% at +30°C (+86°F)
60 Ω maximum
Up to eight inputs; input contacts can be normally open (NO) or normally
closed (NC) with appropriate EOL resistors for supervision.
Address 102: DX2010 occupies Points 9 to 16
Address 103: DX2010 occupies Points 17 to 24
Address 104: DX2010 occupies Points 25 to 32
System Reference Guide
Device Specifications and Overview | en
Description
Alarm memory announcement (if system is on).
At least one point is faulted or bypassed; no trouble exists.
73