Easy Series Control Panel
Wireless Sensitivity (9018 ... 9328): Points 1 - 32 = 0
Alarm Verification (9016 ... 9326): Points 1 - 32 = 0
Table 5.2: Manuf. Default for Point Programming Items
5.2.7
Output Programming Items
Programming Item
Fire Output Cadence
Output 1 Function (wired)
Output 2 Function (wired)
Output 3 Function (wired)
Output 4 Function (wired)
Output 4 Supervised Speaker Driver
(wired)
Default = Country-specific default. Select this programming item to hear the updated default value, or refer to
Country Code Specific Default Programming Codes, page 112.
See also
–
Bosch Security Systems, Inc.
Item
Number
600
611
621
631
641
642
Country Code Specific Default Programming Codes, page 112
System Reference Guide
Selections
0 = Temporal Code 3 cadence
1 = Pulse cadence
(two-sec on, two-sec off)
0 = Disabled
1 = Intrusion
2 = Intrusion Latching
3 = Fire
4 = Fire Latching
5 = Intrusion and Fire
6 = Intrusion and Fire Latching
7 = System Reset
8 = System On
9 = System Ready
10 = Key Fob On/Off
11 = Key Fob 2-sec Pulse
13 = User Controlled
14 = Interior Intrusion and Fire
15 = System On (Unoccupied)
16 = Intrusion and Fire 2
0 = Supervised 8 Ω speaker driver
1 = Unsupervised open collector
Programming | en
59
Manuf.
Defaul
t
0
5
5
5
7
0
2014.09 | 01 | F.01U.306.221