58
en | Programming
Programming Item
Number
(bold digits = Point
Number)
9013, 9023, 9033,
9043...9103...9153...9203..
.9323
9014, 9024, 9034,
9044...9104...9154...9204..
.9324
9015, 9025, 9035,
9045...9105...9155...9205..
.9325
9016, 9026, 9036,
9046...9101...9151...9201..
.9321
9018, 9028, 9038,
9048...9108...9158...9208..
.9328
Point Type (9011 ... 9321): Point 1 = 6, Points 2 - 5 = 1, Points 6 - 8 = 2, Points 9 - 32 = 0
Circuit Style (9012 ... 9322): Points 1 - 32 = 2
Custom Protection (9013 ... 9323): Points 1 - 32 = 0
Cross Zone Enabled (9021 ... 9321): 1
Response Time (9015 ... 9085): Points 1 - 8 only = 6
2014.09 | 01 | F.01U.306.221
Programming Item
Include in Custom Protection
Cross Zone/Exit Route
Response Time
Alarm Verification
Wireless Detector Sensitivity
System Reference Guide
Selections
0 = Point not included
1 = Point included
0 = Cross zoning disabled, point is on the exit
route.
1 = Cross zoning enabled, point is on the exit
route
2 = Cross zoning disabled, point is not on the
exit route (must force arm).
3 = Cross zoning enabled, point is not on the
exit route.
1 to 10 in 50 ms increments
0 = Disable alarm verification
1 = Enable alarm verification
Motion Detector (PIR and dual)
0 = Standard
4 = Intermediate
Inertia Detector: Gross Attack Options
0 = Tap off, low sensitivity
1 = Tap off, low/medium sensitivity
2 = Tap off, medium/high sensitivity
3 = Tap off, high sensitivity
Inertia Detector: Minor Attack Options
8 = Tap on, 8 taps, low sensitivity
9 = Tap on, 8 taps, low/medium sensitivity
10 = Tap on, 8 taps, medium/high sensitivity
11 = Tap on, 8 taps, high sensitivity
12 = Tap on, 4 taps, low sensitivity
13 = Tap on, 4 taps, low/medium sensitivity
14 = Tap on, 4 taps, medium/high sensitivity
15 = Tap on, 4 taps, high sensitivity