Dx2010 Point Expander Module; Dx2010 Overview; Dx2010 Installation; Figure 13: Installing The Dx2010 In D203 Enclosure - Bosch D6412 Operation And Installation Manual

Hide thumbs Also See for D6412:
Table of Contents

Advertisement

8.2

DX2010 Point Expander Module

8.2. 1

DX2010 Overview

You can connect up to five DX2010 Point Expander Modules to the D6412 (three to the D4412). In the single point
configuration, each DX2010 adds eight points to the system. In the doubled point configuration, each DX2010 adds 16 points
to the system. Table 7 shows how the DX2010 Point Expander sensor loops are assigned to point locations.
• Current Draw without Aux Output Terminals: 35 mA Standby
• Current Draw with Aux Output Terminals: 135 mA maximum with connected accessories
Review the Section 5.0 Power Outputs to be sure you provide enough power for the Point Expander Modules and any other
powered devices you connect to the panel.
Refer to the DX2010 Installation Guide (P/N: 46413) for complete installation, addressing and operating instructions.
8.2.2

DX2010 Installation

Failure to follow the mounting instructions in this guide may result in damage to
the module.
The DX2010 contains static-sensitive components and must be handled with care. Follow
antistatic procedures when handling the modules.
The DX2010 Module can be mounted in a D203 Enclosure. Mount the module in the
enclosure as shown in Figure 13.
You can also install the DX2010 board in the control panel's enclosure. The D2203 enclosure
can hold up to five DX2010 modules (see Figures 14 and 15).
Enclosure Wall
DX2010
Terminals
© 2003 Bosch Security Systems
DX2010 Side
Mounting Locations
Mounting Hardware
(supplied w/DX2010)

Figure 14: Installing the DX2010 in the Panel Enclosure

D6412/D4412 Operation and Installation Guide
Page 33
D6412/D4412
Off-Board Sensor Loops
Figure 13: Installing the DX2010
in D203 Enclosure
D6412/D4412 PCB
JP1
AUXILIARY
Installer
R
R1
JP2-PO1
T1
Select
R
T
Y
G
B
Alrm
PO1
+
-
+
A
B
L-1
Com
L-2
L-3
Com
L-4
L-5
Com
L-6
L-7
Com
L-8
Install the
module in
the D203
housing
45349E