en | Programming Details and Defaults
880. Alarm Message Minimum Repeat Time
Enter how long the control center waits between alarm message announcements before
repeating the message even if the control center's proximity sensor detects motion.
9xx1. Point Types
2014.09 | 01 | F.01U.306.221
System Reset: Output is normally on. Output turns off for approximately 10 sec when
system is reset. Use this function to supply power to devices such as four-wire smoke
detectors that require power interruption to reset a latching alarm condition
System On: Output turns on when the system is turned on, and remains on until system
is turned off.
System Ready: Output turns on when the system is ready to turn on (no faulted points or
system troubles exist).
Key Fob On/Off: Output turns on or off when the user presses the key fob's arm (lock) or
disarm (unlock) button.
User Controlled: Output turns on or off when a user or the installer uses the Operate
Outputs option from the phone menus.
Interior Intrusion and Fire: Output turns on when an interior intrusion or fire alarm
occurs. To turn off output, turn off system, or wait until end of bell cut-off time. Fire
alarms take priority over intrusion alarms.
System On (Unoccupied): Output turns on when the system is turned On (Unoccupied)
and there are no bypassed or force-armed points.
Intrusion and Fire:
Output turns on when any alarm (Intrusion or Fire) occurs. To turn off the output,
turn off the system, or wait until the end of the bell cut-off time.
When a fire alarm occurs, this output function provides only a steady output (no
Temporal Code 3 or Pulsed cadence).
Fire alarms take priority over Intrusion alarms.
Disabled: Point is disabled.
Perimeter (Entry or Exit): If faulted and the system is on, Entry Delay starts. An alarm
occurs if the system is not turned off when Entry Delay ends.
Interior (Follower) : If the system is on occupied, it ignores these points. If the system is
on unoccupied, a faulted interior point starts an alarm. These points are ignored during
Exit and Entry Delay times.
Perimeter Instant : If faulted when the system is on, a local alarm occurs
24-Hour: If faulted, an alarm always occurs. To restore a 24-hour point, turn the system
off if it is on, or acknowledge the alarm if the system is off.
Fire Verified: If faulted, fire verification occurs. If a second fire event occurs during the
two minute wait period, a fire alarm occurs. If no second fire event occurs, the system
returns to normal.
Fire Instant : If faulted, a fire alarm always occurs.
Silent Panic : If faulted, an alarm always occurs. There is no visual or audio indication of
the alarm.
Interior Walkthrough : If faulted and the system is on custom protection, Entry Delay
starts. If the system is on occupied or unoccupied, this point functions as an interior
point.
Perimeter Exit Cancel : If faulted and restored during Exit Delay, Exit Delay stops and the
system immediately turns on.
Momentary Keyswitch: Turn the system on or off using a momentary keyswitch.
Maintained Keyswitch: Turn the system on or off using a maintained keyswitch.