Section 7 - Gas Burner Conversion Procedures - ALLIANCE AE9133 Service Manual

Ae/ag/ne/ng series home laundry dryers
Table of Contents

Advertisement

Gas Burner Conversion Procedures
For converting dryers equipped for Natural gas to L.P. gas
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the dryer(s) before servicing.
• Close gas shut-off valve to gas dryer(s) before servicing.
• Never start the dryer(s) with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the dryer is properly grounded.
This conversion kit is to be installed by AUTHORIZED DEALERS or DISTRIBUTORS on their
premises and in accordance with the manufacturer's instructions and all codes and
requirements of the authority having jurisdiction. Failure to follow instructions could result in
serious injury or property damage. The qualified agency performing this work assumes
responsibility for this conversion.
401P3 L.P. Gas Conversion Kit consists of:
1 - 58754
Block - Open Plug
1 - 58755
Burner Orifice Spud (Metal stamped
#55)
1 - 60515
Conversion Plate
1 - 60517
Valve Converted to L.P. Gas Sticker
2 - 60520
L.P. Gas Stickers
Gas Input - 20,000 BTU/HR
NOTE: When converting the dryer gas valve to L.P.
gas, be sure the incoming gas supply line is equipped
with a pressure regulator (located ahead of the
dryer) that will maintain the gas supply to the dryer
at 10 ± 1.5 inches (25.4 ± 3.81 cm) water column
pressure and a vent to the outdoors must be
provided. Remove pressure tap pipe plug and check
gas pressure by connecting a "U " tube manometer
(or similar pressure gauge) to the pressure tap .
Refer to Figure 39.
60549
Section 7
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
WARNING
WARNING
Block Open Plug
MANOMETER
DRY962S
Burner Orifice Spud
10 ± 1.5
INCHES
DRY961S
PRESSURE
TAP
Figure 39
W001R1
W312
57