Machine Data - BONFIGLIOLI Act 201 Operating Instructions Manual

Vectron active 201/401 series 230v/400v 0.55 kw ... 132. kw frequency inverter
Hide thumbs Also See for Act 201:
Table of Contents

Advertisement

06/07
06/07
7.2.4

Machine Data

The machine data to be entered during the guided commissioning procedure are indi-
cated on the type plate or the data sheet of the motor. The factory settings of the
machine parameters are based on the nominal data of the frequency inverter and the
corresponding four-pole three-phase motor. The entered and calculated machine data
are checked for plausibility during the guided commissioning procedure. The user
should verify the factory-set rated data of the three-phase motor.
U
I
P
are rated values of the frequency inverter.
FIN,
FIN,
FIN
Parameter
No.
Description
370 Rated Voltage
371 Rated Current
372 Rated Speed
374 Rated Cosinus Phi
375 Rated Frequency
376 Rated mechanical power
Use the arrow keys to select the required parameter and edit the parameter
value.
Use the ENT key to confirm the selected parameter and the parameter values
entered.
Attention! The rated data of the motor are to be entered according to the specifica-
tions on the rating plate for the motor connection type used (star or
delta connection). If the data entered deviate from the rating plate, the
parameters will not be identified correctly. Parameterize the rated data
according to the specifications for the motor winding connection indi-
cated on the rating plate. Take the higher rated current of the connected
asynchronous motor into account.
Operating Instructions ACTIVE
Operating Instructions ACTIVE
Settings
Min.
Max.
0.17⋅U
2⋅U
FIN
FIN
0.01⋅I
10⋅o ⋅ I
FIN
FIN
-1
-1
96 min
60 000 min
0.01
1.00
10.00 Hz
1000.00 Hz
0.01⋅P
10⋅P
FIN
FIN
Fact. sett.
U
FIN
I
FIN
n
N
cos(ϕ)
N
50.00
P
FIN
73
73