In addition to fault messages mentioned, there are further fault messages. However
these messages are only used for internal purposes and are not listed here. If you
receive fault messages which are not listed here, please contact us by phone.
198
198
Code
00
Inside temperature too high, check cooling and fan.
F03
01
Inside temperature too low, check electrical cabinet heating.
Motor temperature too high or sensor defective, check connection
00
S6IND.
F04
01
Motor circuit breaker tripped, check drive.
02
V-belt monitoring reports no load on the drive.
03
Phase failure, check motor and wiring.
00
Overloaded, check load situation and ramps.
03
Short circuit or earth fault, check motor and wiring.
04
Overloaded, check load situation and current value limit controller.
F05
05
Asymmetric motor current, check current and wiring.
06
Motor phase current too high, check motor and wiring.
07
Message from phase monitoring, check motor and wiring.
DC link voltage too high, check deceleration ramps and connected brake
00
resistor.
01
DC link voltage too low, check mains voltage.
02
Power failure, check mains voltage and circuit.
F07
03
Phase failure, check mains fuses and circuit.
Reference DC-Link Limitation
04
05
Brake chopper
06
Motor chopper
01
Electronics voltage 24 V too low, check control terminal.
F08
04
Electronics voltage too high, check wiring of control terminals.
00
Output frequency too high, check control signals and settings.
F11
Max. frequency reached by control, check deceleration ramps and con-
01
nected brake resistor.
00
Earth fault on output, check motor and wiring.
IDC-Compensation Limit
Set
F13
01
increase limit, if necessary.
10
Minimum current monitoring, check motor and wiring.
01
Reference value on multifunctional input 1 faulty, check signal.
07
Overcurrent on multifunctional input 1, check signal.
F14
30
Speed sensor signal defective, check connections S4IND and S5IND.
31
One track of the speed sensor signal is missing, check connections.
32
Direction of rotation of speed sensor wrong, check connections.
Data transmission from control unit KP 500 to inverter failed. In the
F0A
10
control unit must be stored at least 1 file.
The communication module was fitted to slot B without disconnection of
F0B
13
the mains voltage, switch mains voltage off.
Operating Instructions ACTIVE
Operating Instructions ACTIVE
Inside
Meaning
Motor Connection
Output current
DC link voltage
680 too low, check mains voltage.
Trigger Threshold
506 too low, check mains voltage.
Trigger Threshold
507 too low, check mains voltage.
Electronics voltage
Output frequency
Motor Connection
415 reached, check motor and cabling,
Control Connection
Optional Components