Electrical Installation - BONFIGLIOLI Act 201 Operating Instructions Manual

Vectron active 201/401 series 230v/400v 0.55 kw ... 132. kw frequency inverter
Hide thumbs Also See for Act 201:
Table of Contents

Advertisement

5
The electrical installation must be carried out by qualified staff according to the gen-
eral and regional safety and installation directives. For a safe operation of the fre-
quency inverter it is necessary that the documentation and the device specifications
be complied with during installation and commissioning. In the case of special applica-
tions, you may also have to comply with further guidelines and instructions.
Danger!
The connecting cables must be protected externally, considering the maximum volt-
age and current values of the fuses. The mains fuses and cable cross-sections are to
be selected according to EN 60204-1 and DIN VDE 0298 Part 4 for the nominal oper-
ating point of the frequency inverter. According to UL/CSA, the frequency inverter is
suitable for operation at a supply network of a maximum of 480 VAC which delivers a
maximum symmetrical current of 5000 A (effective value) if protected by fuses of
class RK5. Only use copper cables with a temperature range of 60/75 °C.
Warning!
Note:
Connection conditions
− The frequency inverter is suited for connection to the public or industrial supply
− It must be checked, based on the specifications of EN 61000-3-2, if the devices
− Operation on unearthed mains (IT mains) is admissible after disconnection of the Y
− Interference-free operation with residual-current device is guaranteed at a tripping
06/07
06/07

Electrical Installation

When the frequency inverter is disconnected from power supply, the
mains, DC-link voltage and motor terminals may still be live for some
time. Wait for some minutes until the DC link capacitors have discharged
before starting to work at the unit.
The frequency inverters are to be grounded properly, i.e. large connec-
tion area and with good conductivity. The leakage current of the fre-
quency inverters may be > 3.5 mA. According to EN 50178 a permanent
connection must be provided. The protective conductor cross-section
required for grounding the fixing plate must be at least 10 mm², or a
second protective conductor must be installed electrically parallel to the
first one. In these applications, the cross-section must correspond to the
recommended cross-section of the wire.
The degree of protection IP20 can only be reached if the terminals are
fitted on the frequency inverter and the covers are properly mounted.
mains according to the technical data. If the transformer output of the supply
mains is ≤ 500 kVA, the optional mains commutation choke is only necessary for
the frequency inverters identified in the technical data. The other frequency invert-
ers are suitable for connection without a mains commutating choke with a relative
mains impedance ≥ 1%.
can be connected to the public supply means without taking additional measures.
The frequency inverters ≤ 9.2 kW with integrated EMC filter comply with the emis-
sion limits of the product standard EN 61800-3 up to a motor cable length of 10 m,
without additional measures being required. Increased requirements in connection
with the specific application of the frequency inverter are to be met by means of
optional components. Commutating chokes and EMC filters are optionally available
for the series of devices.
capacitors in the interior of the device.
current ≥ 30 mA if the following points are observed:
Pulse-current and alternating-current sensitive residual current devices (Type
A to EN 50178) in the case of a connection of frequency inverters with one-
phase power supply (L1/N)
All-current sensitive residual current devices (Type B to EN 50178) in the case
of a connection of frequency inverters with two-phase (L1/L2) or three-phase
(L1/L2/L3) power supply.
Use EMC filters with reduced leakage current or, if possible, do not use EMC
filters at all.
The length of the shielded motor cable is ≤ 10 m and there are no additional
capacitive components between the mains or motor cables and PE.
Operating Instructions ACTIVE
Operating Instructions ACTIVE
31
31