5.4
5.4.1
Dimension the wire according to the electrical load and applied voltage. Use a suitable
conductor cross section to reduce the voltage drop at the wire. The motor can not
obtain the full torque if the voltage drop at the wire is too high. Comply to the coun-
try-specific and application-specific regulations and to the UL-Notes. Suitable fuse
protection values for the mains connection are listed in the chapter "Technical data".
Dimension the conductor cross section of the protective conductor (PE) according to
EN 61800-5-1:
5.4.1.1
The following tables give an overview with typical conductor cross sections (copper
cable with PVC insulation, 30 °C ambient temperature, continuous mains current
maximum 100% of rated mains current). Dependening on the operation conditions
other conductor cross sections may be applicable.
230 V: one-phase (L/N) and two-phase (L1/L2) connection
230 V: three-phase connection (L1/L2/L3)
06/07
06/07

Connection of the device

Dimensioning of the conductor cross section

Mains cable cross section
Up to 10 mm²
10...16 mm²
16...35 mm²
> 35 mm²

Typical conductor cross sections

ACT 201
Mains cable
0.55 kW
-05
0.75 kW
-07
1.5 mm²
1.1 kW
-09
1.5
-11
2.2 kW
-13
2.5 mm²
3 kW
-15
4 kW
-18
ACT 201
Mains cable
0.55 kW
-05
0.75 kW
-07
1.1 kW
-09
1.5 mm²
1.5 kW
-11
2.2 kW
-13
3 kW
-15
4 kW
-18
5.5 kW
-19
7.5 kW
-21
9.2 kW
-22
Operating Instructions ACTIVE
Operating Instructions ACTIVE
Protective conductor (PE)
Instal two protective conductors with the same
conductor cross section as for the mains cable or
2
10 mm
conductor cross section.
Instal a protective conductor with the same con-
ductor cross section as for the mains cable.
Instal a protective conductor with 16 mm² conduc-
tor cross section.
Instal a protective conductor with the half cross
section of the mains cable cross section.
PE-conductor
2x1.5 mm² or
1x10 mm²
2x2.5 mm² or
1x10 mm²
2x4 mm² or
4 mm²
1x10 mm²
PE-conductor
2x1.5 mm² or
1x10 mm²
2x4 mm² or
4 mm²
1x10 mm²
2x 6 mm² or
6 mm²
1x10 mm²
10 mm²
1x10 mm²
Motor cable
1.5 mm²
1.5 mm²
4 mm²
Motor cable
1.5 mm²
4 mm²
6 mm²
10 mm²
35