3
For usage of the expansion module comply with the technical data of the basic de-
vice.
X410A.1
X410A.2
X410A.3
X410A.4
X410A.5
X410A.6
X410A.7
1)
2)
Resolver:
Number of pole pairs: 1 ... 7
Input voltage 7 V
Input frequency 8 kHz
Input current <= 60 mA
U
in
Warning! The PTC input is not insulated. Only PTC thermistors with safe insulation
Note:
Digital inputs (X410B.2) ... (X210B.4):
Low signal: 0 V ... 3 V, High signal: 12 V ... 30 V, Input resistance: 2.3 kΩ,
Response time: 4 ms, PLC compatible
Frequency signal: 0 ... 30 V, 10 mA at 24 V, fmax = 150 kHz
Digital outputs (X410A.3), (X410A.4):
Low signal: 0 V ... 3 V,
High signal: 12 V ... 30 V, output current: 40 mA, PLC compatible
Analog input (X410A.6):
Analog signal: input voltage: -10 V ... 10 V / 0 V ... 10 V (R
Resolution 10 Bit
DC-24 V output (X410A.1):
I
max
of the basic device and expansion module.
Conductor cross section:
Suitable cross sections of the control terminals are:
With wire end ferrule:
Without wire end ferrule:
8
8
Technical data of the expansion module EM-RES-03
Terminal X410A
DC-24 V output
(max. 180 mA)
Ground 24 V
Digital output EM-S1OUTD
Digital output EM-S2OUTD
Not connected.
Analog input EM-S1INA
Ground 10 V
The power supply at terminal X410A.1 may be loaded with a maximum current of
I
= 180 mA. Relative to the application, the maximum current available will be
max
reduced by the further control outputs of the frequency inverter and expansion
module.
The control electronics can be freely parameterized.
Resolver- and PTC-input X412 (SubD-9)
RMS
/U
= 0.5
ref
from the motor winding acc. to EN61800-5-1 may be connected.
BONFIGLIOLI servomotors of types BCR and BTD are designed with safe
insulation from the motor winding.
Technical data of the control terminals
= 180 mA. This value can be lower dependent on the load at the digital outputs
X410B.1
1)
X410B.2
2)
X410B.3
2)
X410B.4
X410B.5
2)
X410B.6
X410B.7
PTC input 2)
Tripping resistance = 2.4 kΩ acc. DIN 44081
Hysteresis = 1.3 kΩ
PTC thermistor respectively
bimetallic temperature sensor (normally closed
contact)
0.25...1.0 mm²
0.14...1.5 mm²
EM-RES-03
EM-RES-03
Terminal X410B
Not connected.
Digital input EM-S1IND
Digital input EM-S2IND
Digital input EM-S3IND
System bus, CAN-Low
System bus, CAN-High
Ground 10 V
= 100 kΩ),
i
10/07
2)
2)
2)
10/07
Need help?