in the following chapter. The data are polled in accordance with the table below.
7.2.4
The machine data to be entered during the guided commissioning procedure are
indicated on the type plate or the data sheet of the motor. The factory settings of the
machine parameters are based on the nominal data of the frequency inverter and the
corresponding four-pole three-phase motor. The entered and calculated machine data
are checked for plausibility during the guided commissioning procedure. The user
should verify the factory-set rated data of the three-phase motor.
U
No.
370 Rated Voltage
371 Rated Current
372 Rated Speed
374 Rated Cosinus Phi
375 Rated Frequency
376 Rated Mech. Power
Attention! The rated data of the motor are to be entered according to the
7.2.5
After the machine data (and the speed sensor data, if applicable) have been entered,
the calculation or examination of the parameters is started automatically. The display
changes over to "CALC" for a short time. If the verification of the machine data is
successful, the guided commissioning procedure continues with the identification of
the parameters.
Verification of the machine data should only be skipped by experienced users. The
configurations contain complex control processes which depend to a large degree on
the correctness of the machine parameters entered.
06/05
06/05
Operation mode
0 - Unknown
1 - Asynchronous
2 - Synchronous
3 - Reluctance
10 - Transformer

Machine Data

I
P
are rated values of the frequency inverter.
FUN,
FUN,
FUN
Parameter
Description
Use the arrow keys to select the required parameter and edit the parameter
value.
Use the ENT key to confirm the selected parameter and the parameter values
entered.
specifications on the rating plate for the motor connection type used
(star or delta connection). If the data entered deviate from the rating
plate, the parameters will not be identified correctly.

Plausibility check

Function
The motor is not a standard type.
Three-phase asynchronous motor, squirrel cage
Three-phase synchronous motor
Three-phase reluctance motor
Transformer with three primary windings
Min.
0.17⋅U
FUN
0.01⋅I
FUN
-1
96 min
0.01
10.00 Hz
0.01⋅P
FUN
Settings
Max.
Fact. sett.
2⋅U
U
FUN
FUN
10⋅o ⋅ I
I
FUN
FUN
-1
60 000 min
n
N
1.00
cos (ϕ)
1000.00 Hz
50.00
10⋅P
P
FUN
FUN
N
41
41