400 V: three-phase connection (L1/L2/L3)
5.4.2
The mains fuses and cable cross-sections are to be selected according to EN 60204-1
and DIN VDE 0298 Part 4 for the nominal operating point of the frequency inverter.
According to UL/CSA, approved Class 1 copper lines with a temperature range of
60/75°C and matching mains fuses are to be used for the power cables. The electrical
installation is to be done according to the device specifications and the applicable
standards and directives.
Caution!
36
36
ACT 401
Mains cable
0.55 kW
-05
0.75 kW
-07
1.1 kW
-09
1.5 kW
-11
1.5 mm²
1.85 kW
-12
2.2 kW
-13
3 kW
-15
4 kW
-18
5.5 kW
-19
2.5 mm²
7.5 kW
-21
9.2 kW
-22
11 kW
-23
15 kW
-25
18.5 kW
-27
22 kW
-29
30 kW
-31
37 kW
-33
45 kW
-35
55 kW
-37
65 kW
-39
75 kW
-43
90 kW
-45
110 kW
-47
2x70 mm²
132 kW
-49
2x95 mm²

Mains Connection

The control, mains and motor lines must be kept physically separate
from one another. The cables connected to the frequency inverters may
not be subjected to high-voltage insulation tests unless appropriate cir-
cuitry measures are taken before. Otherwise the unit may be damaged.
Operating Instructions ACTIVE
Operating Instructions ACTIVE
PE-conductor
2x1.5 mm² or
1x10 mm²
2x2.5 mm² or
1x10 mm²
2x4 mm² or
4 mm²
1x10 mm²
2x6 mm² or
6 mm²
1x10 mm²
10 mm²
1x10 mm²
16 mm²
1x16 mm²
25 mm²
1x16 mm²
35 mm²
1x16 mm²
50 mm²
1x25 mm²
70 mm²
1x35 mm²
95 mm²
1x50 mm²
1x70 mm²
1x95 mm²
Motor cable
1.5 mm²
2.5 mm²
4 mm²
6 mm²
10 mm²
16 mm²
25 mm²
35 mm²
50 mm²
70 mm²
95 mm²
2x70 mm²
2x95 mm²
06/07
06/07