Control Functions; Intelligent Current Limits - BONFIGLIOLI Act 201 Operating Instructions Manual

Vectron active 201/401 series 230v/400v 0.55 kw ... 132. kw frequency inverter
Hide thumbs Also See for Act 201:
Table of Contents

Advertisement

16
The frequency inverters provide a selection of established control methods in
figuration
optimized for the application by further functions.
16.1
The current limits to be set according to the application avoid inadmissible loading of
the connected load and prevent a fault switch-off of the frequency inverter. The func-
tion extends the current controller available in the control system. The overload re-
serve of the frequency inverter can be used optimally by means of the intelligent cur-
rent limits, in particular in applications with dynamic load alternations. The criterion to
be selected via the parameter
vation of the intelligent current limit. The parameterized rated motor current or the
reference current of the frequency inverter is synchronized as the limit value of the

intelligent current limits.

10 - Tc
11 - Ixt + Tc
20 - Motor Temp.
21 - Motor Temp.+ Ixt
30 - Tc + Motor Temp.
31 -
The threshold value selected via the parameter
the intelligent current limits. In the operation modes with motor and heat sink tem-
perature monitoring, the reduction of power selected with the parameter
574 is done when the threshold value has been reached. This is achieved by a reduc-
tion of the output current and the speed in motor operation. The load behavior of the
connected machine must be a function of the speed to ensure a sensible use of the
intelligent current limits. The total time of the power reduction as a result of an in-
creased motor or heat sink temperature contains not only the cooling time, but also
the additionally defined
The definition of the power limit should be selected as small as possible in order to
give the drive sufficient time to cool down. The reference value is the nominal power
of the frequency inverter or the set rated power of the motor.
No.
574 Power Limit
575 Limitation Time
In the operation modes with overload reserve (Ixt) there is a reduction of the output
current when the threshold value is exceeded, with a distinction being made between
long and short-term overload reserve. After the short-term overload (1 s) has been
used up, the output current is reduced to the long-term overload current matching the
present switching frequency. After the long-term overload current has been used up
(60 s), the output current is reduced to the rated current which also depends on the
switching frequency. If the output current has already been reduced due to the fact
that the long-term overload has used up, the short-term overload is no longer avail-
able even if it has not been used up beforehand. The defined overload reserve (Ixt) of
the frequency inverter is available again after a power reduction lasting 10 minutes.
158
158

Control Functions

30. The selected control structure can be parameterized as required and
Intelligent current limits
Operation mode
0 - Off
1 - Ixt
Tc + Motor Temp.
+ Ixt
Limitation Time
Parameter
Description
Operating Instructions ACTIVE
Operating Instructions ACTIVE
Operation Mode
573 defines the threshold to the acti-
The function is switched off.
Limitation to the overload of the frequency inverter (Ixt).
Limitation to the maximum heat sink temperature (T
Operation mode 1 and 10 (Ixt + T
Limitation to the motor temperature (T
Operation mode 20 and 1 (T
Operation mode 10 and 20 (T
Operation mode 10, 20 and (T
Operation Mode
575.
Min.
40.00 %
5 min
Function
).
C
).
Motor
+ Ixt).
Motor
+ T
).
C
Motor
+ T
+ Ixt).
C
Motor
573 is monitored by
Power Limit
Settings
Max.
Fact. sett.
95.00 %
300 min
Con-
).
C
80.00 %
15 min
06/07