5.13
Selecting forward and reverse runs (operation panel only)
: Forward/reverse run selection
• Function
Program the direction of rotation of the motor when the running and stopping are made using the RUN key and
STOP key on the operation panel.
Valid when (command mode selection) = (operation panel input).
[Parameter setting]
Title
Forward/reverse run selection
Check the direction of rotation on the status monitor.
: Forward run
For monitoring, refer to Section 8.1.
When the F and R terminals are used for switching between forward run and stop from the terminal board, the
forward/reverse run selection parameter is rendered invalid.
Short across the F-CC terminals: forward run
Short across the R-CC terminals: reverse run
If F and CC, as well as R and CC are connected at the same time: Stop (Default setting)
Use the parameter to select between reverse run and stop in this case.
For more details, refer to Section 6.2.1.
This function is valid only when is set at (Operation panel input enabled).
To switch between forward run and reverse run from the control panel with parameter set to or , perform
these steps: to switch to forward run, press the
reverse run, press the
Function
: Forward run
: Reverse run
: Forward run (F/R switching possible)
: Reverse run (F/R switching possible)
: Reverse run
key while holding the
key while holding
key down.
ENT
E-21
Adjustment range
key down, or to switch to
ENT
E6581442
Default setting
5