Operation in automatic torque
boost mode or vector control
mode
(=, , , , )
Is the motor Toshiba standard
four-pole motor with the same
capacity rating as the inverter?
Is the motor cable 30m or less
in length? *1
NO
Set the following parameters, as specified on the motor nameplate.
Nameplate
Title
Setting range
information
~Hz
Base frequency
~ (200V)
Base frequency
~ (400V)
voltage
Rated capacity
~kW
of motor
Motor rated
~A
current
~
Motor rated
speed
min-1
Set at *2
(After execution, the setting returns
to .)
is displayed.
YES
The base frequency or the rated
rotational speed of the motor is
not set correctly. Check their
settings.
Enter the correct value for
or , and then set
to again.
The following parameters have
been calculated and set.
Motor constant 1
Motor constant 2
Motor constant 3
Motor constant 4
*1:
Motor used
Type
No. of motor poles
Toshiba
4P
standard
Other than 4P
motor
Others
* When using a long cable (guide: 30m or over), be sure to make auto-tuning 1 (=).
YES
*2: No problem even if the motor is not connected.
*3: It does not matter whether the motor is under load or no-load
conditions.
*4: As for models 200V-55kW or more and 400V-90kW or more,
NO
Is the motor actually
connected and in a
standby state?
YES
Check the precautions to be taken whe
n setting the auto tuni n g parameter to
1, and if no problem i s found, then set
to and start operation.
or
is displayed.
NO
and have been
tuned to the motor connected.
Capacity
Same as the inverter capacity
Different from the inverter capacity
Same as the inverter capacity
Different from the inverter capacity
F-39
End
also " " and " "is set.
For details of each parameter,
see the next page.
*3
NO
Make necessary settings, as
specified in (1) Setting auto-tuning.
YES
*4
Parameters and
use the value
calculated automatically by the
End
Tuning required or not
(Yes in flowchart: Tuning required, No: Tuning not required)
* Not required (tuned to factory defaults)
Required
E6581442
6
End
End