[25] Protection functions [2/2]
Communi
Title
cation
Function
No.
0622
Abnormal speed detection time

Overspeed detection frequency
0623

upper band
Overspeed detection frequency
0624

lower band
0625
Undervoltage detection level

0626
Overvoltage limit operation level 100~150%

0627
Undervoltage trip selection

Undervoltage (trip alarm)
0628

detection time
Regenerative power ride-through
0629

control level
0630
Braking answer waiting time

0631
Temperature detection

VI/II analog input wire breakage
0633

detection level
Annual average ambient

0634
temperature (calculation for part
replacement alarms)
Rush current suppression relay

0635
activation time

0637
PTC1 thermal selection

0638
PTC2 thermal selection
Braking resistance overload

0639
time (10 times of rated torque)
Step-out detection current level
0640

(for PM motors)
Step-out detection time (for PM
0641

motors)
Brake-equipped motor restart
0643

condition selection
Control power supply backup

0647
option failure monitoring
*1:  For details, refer to Instruction Manual (E6581339) specified in Section 6.42.
Adjustment range
0.01~100.0 sec.
0.0:Disabled, 0.1~30.0Hz
0.0:Disabled, 0.1~30.0Hz
50~79%, 80: (auto mode)
0:Disabled
1:Enabled
0.01~10.00 sec.
55~100%
0.0:Disabled, 0.1~10.0 sec.
0:Standard (150%-60 sec.)
1:Estimation of temperature
0:None
1~100%
1:-10~+10°C
2:+11~+20°C
3:+21~+30°C
4:+31~+40°C
5:+41~+50°C
6:+51~+60°C
0.0~2.5 sec.
0:Deselect
1:Select
0:Deselect
1:Select
0.1~600.0 sec.
10~150
0.0:Not detect
0.1~25.0
0:Default (no waiting time for frequencies of 10Hz
and less)
1:Conditional (no waiting time for frequencies of
20Hz and less)
0:Control power supply not backed up
1:Control power supply backed up (alarm in the
event of a failure)
2:Control power supply backed up (tripping in the
event of a failure)
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
setting
running
(Panel/Communi
control
cation)
0.01/0.01
0.01
Enabled
●/●
0.1/0.01
0.0
Enabled
●/●
0.1/0.01
0.0
Enabled
●/●
1/1
80
Disabled
●/●
1/1
134
Disabled
●/●
1/1
0
Disabled
●/●
0.01/0.01
0.03
Disabled
●/●
1/1
75
Disabled
●/●
0.1/0.1
0.0
Enabled
●/●
1/1
0
Disabled
-
1/1
0
Enabled
●/●
1/1
3
Enabled
●/●
0.1/0.1
0.0
Disabled
●/●
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
0.1/0.1
5.0
Disabled
●/●
1/1
100
Disabled
-
0.1/0.1
0.0
Disabled
-
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
PM
V/f Constant Reference
Torque
control
control
●/●
6. 33. 13
●/●
6. 33. 13
●/●
6. 33. 13
●/●
6. 33. 15
-
6. 14. 2
●/●
6. 33. 15
●/●
6. 33. 15
●/●
6. 33. 16
-
-
-
6. 33. 17
-
-
-
5. 14
●/●
6. 33. 18
●/●
6. 33. 19
●/●
6. 33. 20
●/●
*1
●/●
*1
●/●
5. 19
-
-
6. 29
-
-
6. 29
●/●
6. 33. 23
●/●
6. 33. 24