Toshiba Tosvert VF-AS1 Instruction Manual page 279

The new high-performance inverter
Hide thumbs Also See for Tosvert VF-AS1:
Table of Contents

Advertisement

[20] Torque limit [2/2]
Communi
Title
cation
Function
No.
Regenerative braking torque
0445

limit 2 level
Power running torque limit 3
0446

level
Regenerative braking torque
0447

limit 3 level
Power running torque limit 4
0448

level
Regenerative braking torque
0449

limit 4 level
Acceleration/deceleration
0451

operation after torque limit
Power running stall continuous
0452

trip detection time
Regenerative braking stall

0453
prevention mode selection
Constant output zone torque

0454
limit selection
Torque reference

0455
polarity selection
*1:  For details, refer to Instruction Manual (E6581331) specified in Section 6.42
[21] Adjustment parameters [1/2]
Communi
Title
cation
Function
No.

0458
Current control proportional gain 0~1000

0460
Speed loop proportional gain
Speed loop stabilization

0461
coefficient

0462
Moment of inertia of load 1
0463
Second speed loop proportional gain 1~9999

Second speed loop stabilization
0464

coefficient
0465
Moment of inertia of load 2

0466
Speed PI switching frequency


0467
Motor oscillation control
Stall prevention control

0468
switching
*1:  For details, refer to Instruction Manual (E6581333) specified in Section 6.42.
Adjustment range
0.0~249.9%, 250.0:Disabled
0.0~249.9%, 250.0:Disabled
0.0~249.9%, 250.0:Disabled
0.0~249.9%, 250.0:Disabled
0.0~249.9%, 250.0:Disabled
0:In sync with acceleration/deceleration
1:In sync with min. time
0.0~1.0 sec.
0:Stall during regenerative braking
1:Not stall during regenerative braking
0:Constant output limit
1:Constant torque limit
0:It is interchangeable so far.
(When reversing,reverses the polarity.)
.
1:The polarity doesn't reverse when reversing
Adjustment range
1~9999
1~9999
0~100
1~9999
0~100
0.0~ Hz
0:Disabled
1:Enabled(Low gain)
2:Enabled(Middle gain)
3:Enabled(High gain)
0: Stall prevention control 1
1: Stall prevention control 2
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
setting
running
(Panel/Communi
control
cation)
0.1/0.01
250.0
Enabled
●/●
0.1/0.01
250.0
Enabled
●/●
0.1/0.01
250.0
Enabled
●/●
0.1/0.01
250.0
Enabled
●/●
0.1/0.01
250.0
Enabled
●/●
1/1
0
Disabled
●/●
0.1/0.1
0.0
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
(Panel/Communi
setting
running
control
cation)
1/1
0
Disabled
●/●
1/1
12
Enabled
●/●
1/1
100
Enabled
●/●
1/1
35
Enabled
●/●
1/1
12
Enabled
●/●
1/1
100
Enabled
●/●
1/1
35
Enabled
●/●
1/1
0.0
Enabled
●/●
1/1
0
Disabled
-/-
1/1
0
Disabled
-/-
PM
V/f Constant Reference
Torque
control
control
●/●
-
6. 25. 1
●/●
-
6. 25. 1
●/●
-
6. 25. 1
●/●
-
6. 25. 1
●/●
-
6. 25. 1
-
-
6. 25. 2
-
6. 26. 1
-
6. 26. 2
●/●
-
6. 25. 1
●/●
-
*1
PM
Torque
V/f Constant Reference
control
control
●/●
-
-
*1
-
-
-
*1
-
-
-
*1
-
-
*1
-
-
-
*1
-
-
*1
-
-
*1
-
-
-
*1
-/-
-
6.27.2
-/-
-