(*1): Model in square brackets is fitted with top cover.
(*2): To use a 400V/200kW inverter or larger in combination with an external braking resistor (DGP600 series), a braking unit (PB7) with a built-in braking
resistor drive circuit is also needed.
(*3): The options are selected based on the premise that 600V HIV insulated wires (continuous allowable temperature: 75°C) are used.
(*4): Each MSF-****Z model is composed of a reactor, a resistor and a capacitor, and as a guide, use a cable 300m or less in length to connect the
inverter to the motor.
Each MSL-****T model is an output-dedicated surge suppression reactor, and as a guide, use a cable 100m or less in length (or 50m or less for a
shielded cable) to connect the inverter to the motor, although allowable cable lengths vary according to the input voltage.)
(*5): Be sure to connect DC reactor to 200V-55kW and above models and 400V-90kW and above models. (Not necessary for DC power input.)
When a 200V-55kW and above models or 400V-90 to 280kW models is replaced with new one, the reactor (model: DCL-****) used with the current
inverter can be used as-is with the new inverter. In such cases, therefore, you do not need to purchase any reactors in this table.