10.6

Connection of a DC power supply and other electric units

Besides a three-phase commercial power supply, a single-phase 200V power supply (5.5kW or less) and a DC power
supply can be connected to the VFAS1 inverter.
When connecting each of these units, keep in mind the points described in the following sections.

10.6.1 Connection of a single-phase 200V power supply

The table below shows which model to select when operating a three-phase induction motor, using a single-phase
200V power supply (200-240V, 50/60Hz).
Input power
Single phase
200~240V
50/60Hz
Note: Set the parameter  to  (input phase failure detection mode selection: disabled).

10.6.2 When using the inverter along with a DC power supply

Keep the following in mind when connecting a DC power supply to the VFAS1 (PA/+ and PC/- terminals).
Note 1: An optional initial charger (MCR-2550) is needed for middle- and large-capacity models.
Note 2: 200V-75kW and 400V-110kW and above models are needed to change the connecting for the cooling fan.
Note 3: A DC reactor does not need to be connected to the inverter.
 For details about use in combination with a DC power supply, refer to the instruction manual (E6581432) specified
in section 6.42.
Voltage class
Inverter model
VFAS1-2004PL~
VFAS1-2150PM
200V class
VFAS1-2185PM~
VFAS1-2550P
VFAS1-2750P
VFAS1-4007PL~
VFAS1-4185PL
VFAS1-4220PL~
VFAS1-4900PC
VFAS1-4110KPC
400V class
VFAS1-4132KPC~
VFAS1-4220KPC
VFAS1-4280KPC
VFAS1-4355KPC,
VFAS1-4400KPC
VFAS1-4500KPC
Note: Set the parameter  to  (input phase failure detection mode selection: disabled).
Applicable motor (kW)
0.4
0.75
1.5
2.2
3.7
5.5
Initial charger (optional)
No required
MCR-2550×1
MCR-2550×2 (parallel)
No required
MCR-2550×1
MCR-2550×1
MCR-2550×2 (parallel)
MCR-2550×3 (parallel)
MCR-2550×4 (parallel)
MCR-2550×5 (parallel)
J-11
Inverter type
VFAS1-2007PL
VFAS1-2015PL
VFAS1-2022PL
VFAS1-2037PL
VFAS1-2055PL
VFAS1-2075PL
Change to connection of
cooling fan power supply
No required
No required
No required
No required
Required
No required
No required
No required
No required
No required
Required
No required
Required
No required
Required
No required
Required
No required
Required
No required
E6581442
DC reactor
10