Toshiba Tosvert VF-AS1 Instruction Manual page 211

The new high-performance inverter
Hide thumbs Also See for Tosvert VF-AS1:
Table of Contents

Advertisement

 Output terminal function (open collector, relay outputs) setting and detection levels
For the open connector output terminals (OUT1, OUT2) and the relay output terminals (FLA, FLB and FLC),
functions can be selected from 0 to 255 functions. The selectable functions and detection levels are listed in the
table below.
Up to 7 output terminals can be used if add-on options are used in combination with the inverter, while up to 3
output terminals can be used if no add-on option is used.
<Technical terms>
• Alarm
• Pre-alarm
• Serious failure ·······Output signal in a serious failure of the protection function of the inverter.
• Light failure
• Emergency stop ·······Output signal when the inverter comes into emergency stop.
Table of output terminal functions and detection levels
Parameter setting
Positive
logic


7












·······Alarm output beyond a certain setting value.
·······Alarm output of the state where the inverter may carry out a trip by continuation.
(Arm overcurrent (  , ,  ), Load side overcurrent (  ), Short-circuiting
(  ,  ), Phase failure ( ,  ), Abnormal output current detection
(  ))
·······Output signal in a slight failure of the protection function of the inverter.
(Overload (  ,  ), overvoltage (  ,  ,  ), overcurrent during
acceleration/deceleration/fixed speed operation (  ,  ,  ,  ,  ,  ))
Stopping manner is set with  (emergency stop).
Function
Negative
logic
Lower limit frequency

(LL)
Upper limit frequency

(UL)
Low-speed signal

Acceleration/decelerat

ion completion
Speed reach signal

Failure FL

(All trips)
Failure FL

(Except EF, OCL)
Overcurrent (OC)

pre-alarm
Inverter overload

(OL1) pre-alarm
Motor overload (OL2)

pre-alarm
Overheat pre-alarm

Overvoltage

pre-alarm
Undervoltage in main

circuit (MOFF)
detection
Low current detection

Operation output specifications (in case of positive logic)
ON:The running frequency is equal to or higher than the setting
of  (Lower limit frequency)
OFF:The running frequency is lower than the setting of  .
ON:The running frequency is equal to or higher than the setting
of  (Upper limit frequency)
OFF:The running frequency is lower than the setting of  .
ON:The running frequency is equal to or higher than the setting
of  (low-speed signal output frequency)
OFF:The running frequency is lower than the setting of  .
ON:The difference between the frequency command and the
running frequency is within the setting of  .
OFF:In acceleration or deceleration.
ON:The running frequency is in the range of  ±  .
OFF:The running frequency is out of the range of  ±
 .
ON:Inverter is tripped.
OFF:Inverter trip is canceled.
ON:Inverter is tripped (except  and  )
OFF:Inverter trip is canceled. (reset)
ON:Inverter output current is over the  (Stall prevention
level) set value.
OFF:Inverter output current is under the  .
ON:A certain rate of inverter overload (  ) detection time is
over.
OFF:The detection time is within a certain limit.
ON:A certain rate of inverter overload (  ) detection time is
over.
OFF:The detection time is within a certain limit.
ON:The temperature of the cooling fin is 95°C or higher inside
the inverter.
OFF:The temperature drops to 90°C or lower after overheat
pre-alarm was on.
Overvoltage control operation or PB operation in progress. ON:
PB operation level + 3%
(200V class: Approx. 370Vdc, 400V class :Approx. 740Vdc)
ON:The main circuit voltage is lower than the main circuit
undervoltage detection (  ) level.
(200V class: Approx. 170Vdc, 400V class: Approx. 340Vdc)
ON: The state that inverter output current is  set value or
larger continued more than  set value.
G-6
E6581442

Advertisement

Table of Contents
loading

Table of Contents