Parameter setting
Positive
logic



















7




















Note 1: "ON" in positive logic
"OFF" in positive logic : Open collector output transistor or relay is turned off.
"ON" in negative logic : Open collector output transistor or relay is turned off.
"OFF" in negative logic : Open collector output transistor or relay is turned on.
Note 2: Alarm output check conditions are as follows.
(1) Undervoltage detected :To be checked during operation.
(2) Low current detected
(3) Overtorque detected
 Sink logic/source logic
Sink logic and source logic (logic of input/output terminal) can be switched to each other.
 For details, refer to Section 2.3.2.
Function
Negative
logic
Specified data output

1
Specified data output

2
Specified data output

3
Specified data output

4
Specified data output

5
Specified data output

6
Specified data output

7
 Light load output
 Heavy load output
 Positive torque limit
 Negative torque limit
Output for external rush

suppression relay
Completion of stop

positioning
 L-STOP
Power failure

synchronized operation
 Traverse in progress
Traverse deceleration in

progress
 Part replacement alarm
 Over-torque pre-alarm
Frequency command 1/

2 selection
Failure FL (Except

emergency stop)
Light load signal 1

(VFA7 compatibility)
 My function output 1
 My function output 2
 My function output 3
 My function output 4
 My function output 5
 My function output 6
 My function output 7
 My function output 8
 My function output 9
 My function output 10
 My function output 11
 My function output 12
 My function output 13
 My function output 14
 My function output 15
 My function output 16
Always OFF (for terminal

signal tests)
: Open collector output transistor or relay is turned on.
: To be checked during operation command.
: To be checked always.
Operation output specifications (in case of positive logic)
Output of the designated data in 7-bit.
ON:Load is equal to  ~  set values or less.
ON:Load is larger than  ~  set value.
ON:Positive torque is over the positive torque limit level.
ON:Negative torque is over the negative torque limit level.
ON:External rush suppression relay is actuated.
ON:Stop positioning has been completed.
ON:Operation at the lower limit frequency is performed
continuously.
ON:Power failure synchronized operation is performed.
ON:Traverse operation is performed.
ON:Traverse deceleration operation is performed.
Alarm:The time of replacement of parts is approaching.
ON: 70% of the  or  setting level is detected.
ON:Frequency command selection 2 is selected.
ON:A trip other than emergency stop has occurred.
ON:Load is equal to  ~  set values or less.
ON:My function output 1 is ON.
ON:My function output 2 is ON.
ON:My function output 3 is ON.
ON:My function output 4 is ON.
ON:My function output 5 is ON.
ON:My function output 6 is ON.
ON:My function output 7 is ON.
ON:My function output 8 is ON.
ON:My function output 9 is ON.
ON:My function output 10 is ON.
ON:My function output 11 is ON.
ON:My function output 12 is ON.
ON:My function output 13 is ON.
ON:My function output 14 is ON.
ON:My function output 15 is ON.
ON:My function output 16 is ON.
Output signal always OFF
G-8
E6581442