Analog Outputs - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Output Terminals
8.2

Analog Outputs

Description
The customer terminal block features two analog outputs for outputting setpoints
via current or voltage signals.
Signal Flow Diagram
AO_Signal
p4071
Actual speed
r0063
Output current
r0068
DC-link voltage
r0070
...
Output power
r0082
Fig. 8-1
Signal flow diagram: Analog output 0
Setting Parameters for Analog Output 0 (AO0)
p4071[0]
Signal source for the analog output
Setting parameter for the signal to be output for analog output 0 on the customer terminal block.
p4073[0]
Smoothing time for analog output
Setting parameter for the time constant of the 1
r4074[0]
Current output voltage/current
The current output voltage is displayed in V when analog output 0 is set as a voltage output (p4076 = 1 /
4) and terminals X522: 1 and 2 are used.
The current output current is displayed in mA when analog output 0 is set as a current output (p4076 = 0
/ 2 /3) and terminals X522: 3 and 2 are used.
8-2
Smoothing
p4073
Scaling
Smoothing
st
order low-pass filter for analog output 0.
AO type
p4076
act. V/I
r4074
AO 0V+
D
AO 0A+
A
Current output
AO 0 Bez
Setting range: see list
Factory setting: r1445 (N_ACT)
Setting range: 0 ... 1000 ms
Factory setting: 0 ms
Unit: V or mA
11/03
Voltage
output
X522.1
+-10V
X522.3
+-20mA
X522.2
SINAMICS G150
Operating Manual