Siemens SINAMICS G150 Operating Manual page 181

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

11/03
Remedy:
- Reduce permanent load.
- Adapt duty cycle.
- Check rated currents of motor and power section.
See also: r0036, r0206, p0307
Acknowl.:
Immediate
F30011
Power section: Line phase failure detected
Reaction:
OFF1
Cause:
Line phase failure detected by power section.
- Fuse in main power circuit.
Remedy:
Check fuses in main power circuit.
Acknowl.:
Immediate
F30012
Power section: Temperature sensor Heatsink Wirebreak
Reaction:
OFF2
Cause:
The connection to one of the heatsink temperature sensors in the power section is
interrupted.
See also: r0949
Fault value
Bit0: Module duct (electronic module)
(r0949):
Bit1: Intake air
Bit2: AC converter 1
Bit3: AC converter 2
Bit4: AC converter 3
Bit5: AC converter 4
Bit6: AC converter 5
Bit7: AC converter 6
Bit8: DC converter 1
Bit9: DC converter 2
Remedy:
Contact the manufacturer.
Acknowl.:
Immediate
F30013
Power section: Temperature sensor Heatsink Short-circuit
Reaction:
OFF2
Cause:
The heat sink temperature sensor in the motor module is shorted.
Fault value
Bit0: Module duct (electronic module)
(r0949):
Bit1: Intake air
Bit2: AC converter 1
Bit3: AC converter 2
Bit4: AC converter 3
Bit5: AC converter 4
Bit6: AC converter 5
Bit7: AC converter 6
Bit8: DC converter 1
Bit9: DC converter 2
Remedy:
Contact the manufacturer.
Acknowl.:
Immediate
F30017
Power section: Hardware current limit tripped too may times
Reaction:
OFF2
Cause:
The hardware current limit in the various phases (see A30031, A30032, A30033) has tripped
too many times. The maximum permissible number of trips depends on the power section
type.
- Control incorrectly parameterized.
- Fault in motor or in power lines.
- Power lines exceed maximum permissible length.
- Motor load too high.
- Power section defective.
SINAMICS G150
Operating Manual
Diagnosis / Faults and Alarms
10-39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents