Siemens SINAMICS G150 Operating Manual page 218

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Technical Data
Table 12-11 Version C, 380 V – 480 V, part 3
Category
Order no. 6SL3710-
Rated motor output
Rated connection voltage
Rated input current
Rated output current
Base load current
Power loss
Cooling air requirement
Sound pressure level at 50/60
Hz
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Protective earth connection
Fastening screw
Approx. weight (standard
version)
Dimensions (w x h x d)
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
12-10
Unit
1GE37-5CA0
kW
400
V
3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
A
785
A
745
A
725
kW
9.6
m³/s
0.78
dB(A)
70/73
2
mm
2 x 300
2 x (800)
2
mm
8 x 240
8 x (600)
M12 (4 holes)
2
mm
2 x 300
2 x (800)
2
mm
8 x 240
8 x (600)
M12 (4 holes)
M12 (8 holes)
kg
670
mm
600 x 2000 x 600
3NE1 448-2
A
850
3
1GE38-4CA0
1GE41-0CA0
450
560
883
1034
840
985
820
960
10.1
14.4
0.78
1.48
70/73
72/75
4 x 150
4 x 185
4 x (400)
4 x (500)
8 x 240
8 x 240
8 x (600)
8 x (600)
M12 (4 holes)
M12 (4 holes)
4 x 150
4 x 185
4 x (400)
4 x (500)
8 x 240
8 x 240
8 x (600)
8 x (600)
M12 (4 holes)
M12 (4 holes)
M12 (8 holes)
M12
(10 holes)
670
980
600 x 2000 x 600
1000 x 2000 x 600
Circuit-breaker
Circuit-breaker
Operating Manual
11/03
SINAMICS G150

Advertisement

Table of Contents
loading