Technical Data
12.3.4
Cabinet Unit Version C, 660 V – 690 V
Table 12-17 Version C, 660 V – 690 V, part 1
Category
Order no. 6SL3710-
Rated motor output
Rated connection voltage
Rated input current
Rated output current
Base load current
Power loss
Cooling air requirement
Sound pressure level at 50/60
Hz
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
Protective earth connection
Fastening screw
Approx. weight (standard
version)
Dimensions (w x h x d)
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
12-16
Unit
1GH28-5CA0
kW
75
V
3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
A
103
A
85
A
80
kW
1.7
m³/s
0.17
dB(A)
67/68
2
mm
50
(00)
2
mm
2 x 240
2 x (600)
M12 (1 hole)
2
mm
50
(00)
2
mm
2 x 70
2 x (000)
M12 (1 hole)
M12 (2 holes)
kg
225
mm
400 x 2000 x 600
3NE1 022-2
A
125
00
1GH31-0CA0
1GH31-2CA0
90
110
119
141
100
120
95
115
2.1
2.7
0.17
0.17
67/68
67/68
50
70
(00)
(000)
2 x 240
2 x 240
2 x (600)
2 x (600)
M12 (1 hole)
M12 (1 hole)
50
70
(00)
(000)
2 x 150
2 x 150
2 x (400)
2 x (400)
M12 (1 hole)
M12 (1 hole)
M12 (2 holes)
M12 (2 holes)
225
225
400 x 2000 x 600
400 x 2000 x 600
3NE1 022-2
3NE1 224-2
125
160
00
1
Operating Manual
11/03
SINAMICS G150

Advertisement

Table of Contents
loading

Table of Contents