Operation
6.4.2

Control via PROFIBUS

6.4.2.1
General
"DP1 (PROFIBUS)" Diagnostics LED
The PROFIBUS diagnostics LED is located on the front of the control unit (see
Section 6.4) Its statuses are described in the following table.
Table 6-5
Description of the LEDs
Color
State
------
Off
Green
Continuously lit
Green
Flashing 0.5 Hz
Red
Continuously lit
6.4.2.2
Setting the PROFIBUS Address
Two methods are available for setting the PROFIBUS address:
• The address switches (DIP switches) on the front of the control unit behind the
cover plate (see Section 6.4.1).
If you use the address switch, parameter p0918 is read only and displays the
address that is set.
If the switch is reset, the new setting does not become effective until the control
unit is reset.
• Entering parameter p0918 on the operator panel.
You can only do this if the address has been set to 0 or 127 using the address
switch, that is, all switches from S1 to S7 are set to ON or OFF.
In this case, changes become effective immediately.
Table 6-6
Switch
S1
S2
S3
S4
S5
S6
S7
6-32
No voltage applied to control unit
PROFIBUS is ready for communication and cyclic communication is
taking place
PROFIBUS is ready for communication and cyclic communication is
not taking place
At least one PROFIBUS fault is present. PROFIBUS is not ready for
operation (e.g. after power-on)
PROFIBUS address switches
Significance
0
2
= 1
Significance
1
2
= 2
2
2
= 4
3
2
= 8
4
2
= 16
Example
5
2
= 32
6
2
= 64
Description
Technical data
2
0
2
1
2
2
2
3
2
4
2
5
2
6
1
2
4
8
16
32
64
ON
OFF
...
S1
S7
ON
OFF
1
+ 4
+
32
11/03
= 37
SINAMICS G150
Operating Manual