Emergency Off Button (Option L45) - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical Installation
4.9.4

EMERGENCY OFF Button (Option L45)

Description
The EMERGENCY OFF button with protective collar is integrated in the door of the
cabinet unit. The contacts of the button are connected to terminal block –X120.
Category 0 and 1 EMERGENCY OFF functions can be activated in conjunction
with options L57, L59, and L60.
A braking unit may be necessary to achieve the required shutdown times.
Connection
Table 4-19
cabinet door"
Terminal
1
2
3
4
1)
NC: normally closed contact
2)
Factory setting in converter for options L57, L59, and L60
Max. connectable cross-section: 4 mm² (AWG 10)
4-28
Terminal block X120 – checkback contact "EMERGENCY OFF button in
1)
Designation
NC
Checkback contacts of EMERGENCY OFF button in
NC
2)
NC
2)
NC
Technical data
cabinet door
Max. load current: 10 A
Max. switching voltage: 250 V AC
Max. switching capacity: 250 VA
Required minimum load: ≥1 mA