Further Settings for Analog Inputs

Description
In addition to the settings described in Chapter 6.3.2, a function for scaling input
signals is available.
Signal Flow Diagram
V
I
S5.0
I
S5.1
V
X521:1
+
S5.0
AI 0
-
X521:2
Fig. 6-16
Signal flow diagram: Analog input 0
Setting Parameters for Scaling
Value x1 for the analog input
p4057[0]
characteristic
Setting for the x coordinate in V or mA of the first point on the scaling characteristic.
The unit is V when analog input 0 is set as a voltage input (p4056 = 0 / 4) and switch S5.0 is set to "V".
The unit is mA when analog input 0 is set as a current input (p4056 = 2 / 3 / 5) and switch S5.0 is
set to "I".
Value y1 for the analog input
p4058[0]
characteristic
Setting for the y coordinate in % of the first point on the scaling characteristic.
SINAMICS G150
Operating Manual
Type
p4056
Offset
p4063
act. V/I
Char. y2
r4052
p4060
A
D
Char. y1
p4058
(for p4056 = 3 only)
F3505
Wire Break Analog Input
Char. x1
Char. x2
p4057
y
[%]
y
2
x
x
1
y
1
Scaling
Setting range: -20.000 ... +20.000 V or mA
Factory setting: 0.000 mA
Setting range: -1000.00 ... +1000.00 %
Factory setting: 0.00 %
Operation
p4059
Smoothing
p4053
act. value
r4055
y
x
x
2
6-27