Motor Potentiometer - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

11/03
6.3.3

Motor Potentiometer

Description
The digital motor potentiometer enables you to set speeds remotely using
switching signals (+/- keys). This is activated via terminals X520:2 and X520:3.
Provided that a logical 1 is present at terminal -X520:2 (increase setpoint), the
internal counter adopts this setpoint. You can set the integration time (time taken
for the setpoint to increase) via the operator panel using parameter p1047. The
setpoint can be decreased in the same way via terminal -X520:3 (decrease
setpoint). You can set the deceleration ramp via the operator panel using
parameter p1048.
Prerequisite
p1070 = r1050
Proposed Connection Assignment
PROFIBUS/
terminal block
Motor potentiometer UP
Motor potentiometer DOWN
Fig. 6-12
SINAMICS G150
Operating Manual
Main setpoint is specified by motor potentiometer
<MENU> - <parameterization> - <all parameters> - Select
p1070 and set to r1050
-A10 (CU 320)
-A60 (TM31)
X540
1
1: Terminal
X530
block
1
DI 4
X520
DI 0
1
ON/OFF1
DI 1
2
DI 2
3
DI 3
4
Fault ack.
5
6
Circuit proposal
~
~
=
+
=
~
~
M
~
M1
M
Operation
6-23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents