Output Terminals; Power Connections; Connection Cross-Sections And Cable Lengths - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical Installation
4.6

Power Connections

WARNING
• Swapping the input and output terminals can destroy the cabinet unit!
• Swapping or short-circuiting the DC link terminals can destroy the cabinet unit!
• The contactor and relay operating coils that are connected to the same supply
network as the cabinet unit or are located near the cabinet unit must be
connected to overvoltage limiters (e.g. RC elements).
• The cabinet unit must not be operated via a residual current operated device
(DIN VDE 0160).
4.6.1

Connection Cross-Sections and Cable Lengths

Connection Cross-Sections
The connection cross-sections for the input power connection, motor connection,
and cabinet grounding for your cabinet unit are specified in the tables provided in
the "Technical Data" section.
Cable Lengths
The following table shows the maximum permissible cable lengths (with output filter
(option L08) and without output filter) for standard cable types or cable types
recommended by SIEMENS. Longer cables can only be used after consultation.
The cable lengths specified represent the actual distance between the cabinet unit
and the motor, taking into account parallel routing, current-carrying capacity, and
the cable-laying factor.
Table 4-1
Cabinet unit
Voltage
380 - 480 V
380 - 480 V
660 - 690 V
380 - 480 V
380 - 480 V
660 - 690 V
4-10
Max. permissible cable lengths
Output
Protoflex
EMC 3 Plus
110 kW
300 m
132 - 560 kW 300 m
75 - 800 kW 300 m
110 kW
300 m
132 - 560 kW 300 m
75 - 800 kW 300 m
w/o output filter
Shielded cable
(e.g. Protodur NYCWY)
200 m
300 m
100 m
with output filter
300 m
Not required up to 300
m
200 m
11/03
Unshielded cable
(e.g. Protodur NYY)
300 m
450 m
150 m
450 m
Not required up to
450 m
300 m
SINAMICS G150
Operating Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents