Siemens SINAMICS G150 Operating Manual page 55

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

11/03
S5: Selector for Voltage/Current AI0, AI1
Table 4-11
Selector for voltage/current S5
Switch
S5.0
Selector voltage/current AI0
S5.1
Selector voltage/current AI1
X522: 2 Analog Outputs, Temperature Sensor Connection
Table 4-12
Terminal block X522
Terminal
1
2
3
4
5
6
7
8
1)
AO: analog output; KTY: temperature sensor connection
Max. connectable cross-section: 1.5 mm² (AWG 14)
X540: Common Auxiliary Voltage for Digital Inputs
Table 4-13
Terminal block X540
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 1.5 mm² (AWG 14)
SINAMICS G150
Operating Manual
Function
1)
Designation
AO 0 V+
AO 0 ref.
AO 0 A+
AO 1 V+
AO 1 ref.
AO 1 A+
KTY+
PTC: R
KTY-
Designation
P24
P24
P24
P24
Imax = 150 mA (total of all P24
P24
P24
P24
P24
Technical data
V
V
Voltage
Technical data
-10 V - +10 V
+4 mA - +20 mA
-20 mA - +20 mA
0 mA - +20 mA
KTY84: 0...200 °C
≤ 1.5 kΩ
PTC
Technical data
24 V DC
terminals)
Electrical Installation
I
S5.0
I
S5.1
Current
Factory Setting
Actual speed value:
0 – 20 mA
Motor current actual
value:
0 – 20 mA
Factory Setting
4-23

Advertisement

Table of Contents
loading