11/03
Current fault in: 33463512
F7011 Drv: Motor Overtemp.
Help
Old
F1
F2
F3
Fig. 6-6
Fault screen
Alarm memory
A7850
External warning 1
A7910
Drv: Motor Overtemp.
A7852
External warning 3
Help
Delete
F1
F2
F3
Fig. 6-7
Alarm screen
6.2.5

Saving the Parameters Permanently

Description
If parameters have been changed on the operator panel (press OK in the
Parameter Editor to confirm), the new values are initially stored in a volatile
memory (RAM). An "S" flashes in the top right of the display until they are saved to
a permanent memory. This indicates that at least 1 parameter has been changed
and not yet stored permanently.
Two methods are available for permanently saving parameters that have been
changed:
• Call up the Help function from any screen and press F4 EEPROM
• When confirming a parameter setting with OK, press the OK key for > 1s. The
system displays a message asking you whether the setting is to be saved in the
EEPROM.
If you press "Yes", the system saves the setting in the EEPROM. If you press
"No", the setting is not saved permanently and the "S" starts flashing.
In both cases, all changes that have not yet been saved permanently are stored in
the EEPROM.
SINAMICS G150
Operating Manual
Drv: Motor Overtemp.
Fault value: 00000000
Cause:
Motor temperature has reached the
F1
fault threshold parameterized in
(p0605).
Remedy:
Back
Ack.
Back
F4
F5
Status
Antr: Motor Übertemp.
AlarmVal: 00000000
F1
active
Cause:
Motor temperature has exceeded the
alarm threshold parameterized in
p0604.
F5
The reaction set in p0610 is
Back
upd.
F4
F5
F1
F2
F3
Back
F1
F2
F3
Operation
00000000H
F4
F5
00000000(hex)
F4
F5
6-17