Operation
Signal Flow Diagram
-X520:2
-X520:3
Motorpoti max
p1037
Motorpoti min
p1038
Fig. 6-13
Setting Parameters
Motor potentiometer
p1037
maximum speed
Maximum speed entry for the motor potentiometer.
Motor potentiometer
p1038
minimum speed
Minimum speed entry for the motor potentiometer.
Motor potentiometer ramp-up
p1047
time
Ramp-up time entry for the motor potentiometer.
Motor potentiometer ramp-
p1048
down time
Ramp-down time entry for the motor potentiometer.
Motor potentiometer speed
r1050
setpoint downstream of ramp
generator
Display the setpoint downstream of the motor potentiometer.
6-24
increase
Ramp-up time
decrease
y
0 0
p1082
0 1
1 0
1 1
-p1082
Signal flow diagram: Motor potentiometer
Setting range: -210000.000 ... +210000.000 1/min
Factory setting: p1082 (maximum speed)
Setting range: -210000.000 ... +210000.000 1/min
Factory setting: -p1082 (maximum speed)
Setting range: 0.000 ... 1000.000 s
Factory setting: 10.000 s
Setting range: 0.000 ... 1000.000 s
Factory setting: 10.000 s
Unit: 1/min
Ramp-down time
p1047
p1048
x
Motor potentiometer
(implemented via internal
ramp generator)
11/03
MOP.SetpnRG
r1050
SINAMICS G150
Operating Manual