Siemens SINAMICS G150 Operating Manual page 134

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Output Terminals
Example: Changing Analog Output 0 from Current to Voltage Output –10 - +10 V
and Setting the Characteristic
X522: 1,2
p4076[0] = 4
p4077[0] = 0.00
p4078[0] = 0.000
p4079[0] = 100.00
p4080[0] = 10.000
Fig: 8-5
8-10
Voltage output present at terminal 1, ground at terminal 2
Set TM31.AO_type [analog output 0] to -10 - +10 V
Set TM31.AO_charac. x1 to 0.00%
Set TM31.AO_charac. y1 to 0.000 V
Set TM31.AO_charac. x2 to 100.00%
Set TM31.AO_charac. y2 to 10.000 V
Example: Setting analog output 0 and the characteristic
11/03
SINAMICS G150
Operating Manual