Advertisement

Electrical Installation
X530: 4 Digital Inputs
Table 4-9
Terminal block X530
Terminal
1
2
3
4
5
6
1)
DI: digital input; M2: ground reference; M: electronic ground
Max. connectable cross-section: 1.5 mm² (AWG 14)
NOTE
An open-circuit input is interpreted as "low".
Terminal M1 must be connected so that the digital inputs can function correctly.
The following solutions are possible:
1) The provided ground reference of the digital inputs, or
2) A jumper to terminal M (Important: electrical isolation for the digital inputs
is revoked as a result).
X521: 2 Analog Inputs (Differential Inputs)
Table 4-10
Terminal block X521
Terminal
1
2
3
4
5
6
7
8
1)
AI: analog input; P10/N10: auxiliary voltage, M: ground reference
Max. connectable cross-section: 1.5 mm² (AWG 14)
CAUTION
The input current of the analog inputs must not exceed 35 mA when current
measurements are performed.
4-22
1)
Designation
DI 4
Voltage: -3 V to 30 V
Current input (typical):
10 mA at 24 V
DI 5
With electrical isolation: Reference
DI 6
potential is terminal M2
High level: 15 V to 30 V
DI 7
Low level: -3 V to 5 V
M2
M
1)
Designation
AI 0+
-10 V - +10 V, R
AI 0-
-20 mA - +20 mA, R
AI 1+
AI 1-
+10 V ± 1 %, I
P10
M
Reference potential for AI 0
-10 V ± 1 %, I
N10
M
Reference potential for AI 1
Technical data
Technical data
= 70 kΩ
i
+4 mA - +20 mA
= 250 Ω
i
0 mA - +20 mA
5 mA
max
5 mA
max
11/03
Factory Setting
Command data set
selection CDS bit 0
LOCAL mode disable
Fixed speed setpoint
selection bit 0
Fixed speed setpoint
selection bit 1
Factory Setting
Speed setpoint:
0 – 20 mA
SINAMICS G150
Operating Manual